ASTM G125测量气体氧化剂中液体和固体材料着火极限的标准试验方法

放大字体  缩小字体 发布日期:2012-02-08   浏览次数:58  分享到: 分享到腾讯微博
ASTM G125测量气体氧化剂中液体和固体材料着火极限的标准试验方法
ASTM G125  Standard Test Method for Measuring Liquid and Solid Material Fire Limits in Gaseous Oxidants
ASTM G125测量气体氧化剂中液体和固体材料着火极限的标准试验方法
This test method provides for measuring of the minimum conditions of a range of parameters (concentration of oxidant in a flowing mixture of oxidant and diluent, pressure, temperature) that will just support sustained propagation of combustion. For materials that exhibit flaming combustion, this is a flammability limit similar to the lower flammability limit, upper flammability limit, and minimum oxidant for combustion of gases (1). However, unlike flammability limits for gases, in two-phase systems, the concept of upper and lower flame limits is not meaningful. However, limits can typically be determined for variations in other parameters such as the minimum oxidant for combustion (the oxidant index), the pressure limit, the temperature limit, and others. Measurement and use of these data are analogous to the measurement and use of the corresponding data for gaseous systems. That is, the limits apply to systems likely to experience complete propagations (equilibrium combustion). Successful ignition and combustion below the measured limits at other conditions or of a transient nature are not precluded below the threshold. Flammability limits measured at one set of conditions are not necessarily the lowest thresholds at which combustion can occur. Therefore direct correlation of these data with the burning characteristics under actual use conditions is not implied.
1. Scope
1.1 This test method covers a procedure for measuring the threshold-limit conditions to allow equilibrium of combustion of materials in various oxidant gases under specific test conditions of pressure, temperature, flow condition, fire-propagation directions, and various other geometrical features of common systems.
1.2 This test method is patterned after Test Method D 2863-95 and incorporates its procedure for measuring the limit as a function of oxidant concentration for the most commonly used test conditions. Sections 8, 9, 10, 11, 13, and 14 for the basic oxidant limit (oxygen index) procedure are quoted directly from Test Method D 2863-95. Oxygen index data reported in accordance with Test Method D 2863-95 are acceptable substitutes for data collected with this standard under similar conditions.
1.3 This test method has been found applicable to testing and ranking various forms of materials. It has also found limited usefulness for surmising the prospect that materials will prove “oxygen compatible” in actual systems. However, its results do not necessarily apply to any condition that does not faithfully reproduce the conditions during test. The fire limit is a measurement of a behavioral property and not a physical property. Uses of these data are addressed in Guides G 63 and G 94.
Note 1—Although this test method has been found applicable for testing a range of materials in a range of oxidants with a range of diluents, the accuracy has not been determined for many of these combinations and conditions of specimen geometry, outside those of the basic procedure as applied to plastics.
Note 2—Test Method D 2863-95 has been revised and the revised Test Method has been issued as D 2863-97. The major changes involve sample dimensions, burning criteria and the method for determining the oxygen index. The aim of the revisions was to align Test Method D 2863 with ISO 4589-2. Six laboratories conducted comparison round robin testing on self-supporting plastics and cellular materials using D 2863-95 and D 2863-97. The results indicate that there is no difference between the means provided y the two methods at the 95 % confidence level. No comparison tests were conducted on thin films. The majority of ASTM Committee G4 favors maintaining the D 2863-95 as the backbone of G 125 until comprehensive comparison data become available.
1.4 One very specific set of test conditions for measuring the fire limits of metals in oxygen has been codified in Test Method G 124. Test Method G 124 measures the minimum pressure limit in oxygen for its own set of test conditions. Its details are not reproduced in this standard. A substantial database is available for this procedure, although it is much smaller than the database for Test Method D 2863-95. (Warning—During the course of combustion, gases, vapors, aerosols, fumes or any combination of these are evolved which may be hazardous.) (Warning—Adequate precautions should be taken to protect the operator.)
1.5 The values stated in SI units are to be regarded as the standard. No other units of measurement are included in this standard.
1.6 This basic standard should be used to measure and describe the properties of materials, products, or assemblies in response to heat and flame under controlled laboratory conditions and should not be used to directly describe or appraise the fire hazard or fire risk of materials, products or assemblies under actual fire conditions. However, results of this test may be used as elements of a fire risk assessment which takes into account all of the factors which are pertinent to an assessment of the fire hazard of a particular end use. The standard has more applicability in this regard at predicting the fire behavior of materials and components that are close in size to the test condition, than for systems that are much different (for example: comparing a test rod to a valve seat rather than comparing a test rod to a house or a particle)
1.7 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

2. Referenced Documents (purchase separately)
ASTM Standards
D618 Practice for Conditioning Plastics for Testing
D1071 Test Methods for Volumetric Measurement of Gaseous Fuel Samples
D2444 Test Method for Determination of the Impact Resistance of Thermoplastic Pipe and Fittings by Means of a Tup (Falling Weight)
D2863 Test Method for Measuring the Minimum Oxygen Concentration to Support Candle-Like Combustion of Plastics (Oxygen Index)
G63 Guide for Evaluating Nonmetallic Materials for Oxygen Service
G94 Guide for Evaluating Metals for Oxygen Service
G124 Test Method for Determining the Combustion Behavior of Metallic Materials in Oxygen-Enriched Atmospheres
G128 Guide for Control of Hazards and Risks in Oxygen Enriched Systems
Other Standards
ISO4589-2 Plastics--Determination of burning behavior by oxygen index--Part 2: Ambient temperature test
Index Terms
Fire limit; Fire testing--gases; Flammability limit; Gaseous oxygen systems/service; Oxidant index; Oxygen index; Pressure limit; Promoter/promoted combustion/ignition;


  详情请咨询
  防火资源网-阻燃防火测试中心
  电话:(+86)0592-5056213
  传真:(+86)0592-5105807
  邮件:firetest@firetc.com

凡注明"防火资源网"的所有作品,由<防火资源网>整理编辑,任何组织未经<防火资源网>及其拥有者授权,不得复制、转载、摘编或利用其它方式应用于任何商业行为。

 
 
[ 防火测试中心搜索 ]  [ ]  [ 告诉好友 ]  [ 打印本文 ]  [ 关闭窗口 ]  [ 返回顶部 ]

 

 
 
推荐防火测试
推荐图文
点击排行
 
 
网站首页 | 广告服务 | 关于我们 | 联系方式 | 服务协议 | 版权声明 | 网站地图 | 友情链接 | 网站留言 | 旧版本 | 闽ICP备09009213号
©2019-2021 FIRETC.COM All Rights Reserved   备案号:闽ICP备09009213号-1在线客服 点击QQ交谈/留言 点击QQ交谈/留言