The content of dissolved decay products in insulating oils is made up of a variety of compounds, such as peroxides, aldehydes, ketones, and organic acids. Each of them is partially adsorbed on the large surface of paper insulation leading to the premature aging of power transformers. The relative assessment of byproduct formation, therefore, can be used as an indicator of the aging of the mineral oil.
1. Scope
1.1 This test method characterizes by spectrophotometry the relative level of dissolved decay products in mineral insulating oils of petroleum origin. While new oil is almost transparent to a monochromatic beam of light in the visible spectrum, the increasing concentration of dissolved decay products shift the absorbance curve to longer wavelengths.
1.2 This test method is applicable to compare the extent of dissolved decay products for oils in service. It can assess the effectiveness of used or stored oil purification during the reclamation process, as well.
1.3 The values stated in SI units are to be regarded as standard. No other units of measurement are included in this standard.
1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and to determine the applicability of regulatory limitations prior to use.

2. Referenced Documents (purchase separately)
ASTM Standards
D923 Practices for Sampling Electrical Insulating Liquids
D1524 Test Method for Visual Examination of Used Electrical Insulating Oils of Petroleum Origin in the Field
D3487 Specification for Mineral Insulating Oil Used in Electrical Apparatus
Index Terms
chemical stability; dissolved decay products; insulating oil; oxidation decay; visible spectrum; Chemical stabilization testing; Dissolved decay products; Mineral insulating oil; Oxidation induced defects; Oxidation testing; Spectrophotometry; Visible spectrum;

  详情请咨询
  防火资源网-阻燃防火测试中心
  电话:(+86)0592-5056213
  传真:(+86)0592-5105807
  邮件:firetest@firetc.com

凡注明"防火资源网"的所有作品,由<防火资源网>整理编辑,任何组织未经<防火资源网>及其拥有者授权,不得复制、转载、摘编或利用其它方式应用于任何商业行为。

 
 
[ 防火测试中心搜索 ]  [ ]  [ 告诉好友 ]  [ 打印本文 ]  [ 关闭窗口 ]  [ 返回顶部 ]

 

 
 
推荐防火测试
推荐图文
点击排行
 
 
网站首页 | 广告服务 | 关于我们 | 联系方式 | 服务协议 | 版权声明 | 网站地图 | 友情链接 | 网站留言 | 旧版本 | 闽ICP备09009213号
©2019-2021 FIRETC.COM All Rights Reserved   备案号:闽ICP备09009213号-1在线客服 点击QQ交谈/留言 点击QQ交谈/留言