ASTM C1136隔热用柔性,低渗透蒸气阻化剂的标准规范

放大字体  缩小字体 发布日期:2012-02-13   浏览次数:485  分享到: 分享到腾讯微博
ASTM C1136隔热用柔性,低渗透蒸气阻化剂的标准规范
ASTM C1136 Standard Specification for Flexible, Low Permeance Vapor Retarders for Thermal Insulation
ASTM C1136隔热用柔性,低渗透蒸气阻化剂的标准规范
This specification covers vapor retarders for thermal insulation, specifically, flexible materials with permeance and surface burning characteristics. Vapor retarders are classified based on vapor retardance and strength properties: Types I, II, III, IV, V, and VI. The following test methods shall be performed: water vapor permeance; surface burning characteristics; tensile strength; dimensional stability; fungi resistance; thermal integrity of flexible water vapor retarders; burst strength of vapor retarders; permanence of flame retardancy; and elevated temperature and humidity resistance of vapor retarders for insulation.
This abstract is a brief summary of the referenced standard. It is informational only and not an official part of the standard; the full text of the standard itself must be referred to for its use and application. ASTM does not give any warranty express or implied or make any representation that the contents of this abstract are accurate, complete or up to date.
Significance and Use
Entrapment of water in thermal insulation caused by condensation of water vapor that has penetrated into the insulation is detrimental to the thermal resistance of the insulation. For this reason, in certain installations where temperature and moisture conditions have the potential to create a vapor driving force toward the insulation, a deterrent to the passage of such vapor into the installed insulation needs to be provided. This is the primary function of the vapor retarder.
In addition to the function stated in 9.1, a vapor retarder has the potential to provide physical protection and added strength to the insulation system.
This specification is used to specify material by physical property requirements that address the above prerequisites. The designer of an insulation system, after determining the degree of protection needed for the insulation, can use this specification to specify the appropriate type of vapor retarder when one is required.
1. Scope
1.1 This specification covers vapor retarders for thermal insulation, specifically, flexible materials with permeance of 0.10 perm or lower and surface burning characteristics of 25 flame spread/50 smoke or lower. These materials are intended for use at surface temperatures of −20 to 150°F (−29 to 66°C). It does not cover mastics or barrier coatings applied in liquid form, nor materials intended for use as weather barriers.
1.2 This is a material specification and does not imply that an installed system using these materials will provide the physical properties specified in Section 6.
1.3 This specification provides physical requirements for vapor retarders. Practice C755 provides assistance in solving problems related to moisture vapor transmission through thermal insulation materials.
1.4 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.5 The following precautionary caveat pertains to the test methods portion only, Section 10, of this specification: This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

2. Referenced Documents (purchase separately)
ASTM Standards
C168 Terminology Relating to Thermal Insulation
C755 Practice for Selection of Water Vapor Retarders for Thermal Insulation
C1258 Test Method for Elevated Temperature and Humidity Resistance of Vapor Retarders for Insulation
C1263 Test Method for Thermal Integrity of Flexible Water Vapor Retarders
C1338 Test Method for Determining Fungi Resistance of Insulation Materials and Facings
D774/D774M Test Method for Bursting Strength of Paper
D828 Test Method for Tensile Properties of Paper and Paperboard Using Constant-Rate-of-Elongation Apparatus
D882 Test Method for Tensile Properties of Thin Plastic Sheeting
D1204 Test Method for Linear Dimensional Changes of Nonrigid Thermoplastic Sheeting or Film at Elevated Temperature
E84 Test Method for Surface Burning Characteristics of Building Materials
E96/E96M Test Methods for Water Vapor Transmission of Materials
TAPPI Standards
T461 Flame Resistance of Treated Paper and Paperboard
Index Terms
flexible; low permeance; thermal insulation; vapor retarders; Condensation; Flammability--building materials; Humidity; Low-temperature service applications; Puncture testing; Thermal insulating materials--specifications; Thermal insulating materials (water vapor transmission); Vapor barriers--specifications; Water entrapment; Water vapor retarders--specifications; Water vapor transmission (WVT)--thermal insulation;

  详情请咨询
  防火资源网-阻燃防火测试中心
  电话:(+86)0592-5056213
  传真:(+86)0592-5105807
  邮件:firetest@firetc.com

凡注明"防火资源网"的所有作品,由<防火资源网>整理编辑,任何组织未经<防火资源网>及其拥有者授权,不得复制、转载、摘编或利用其它方式应用于任何商业行为。

 
 
[ 防火测试中心搜索 ]  [ ]  [ 告诉好友 ]  [ 打印本文 ]  [ 关闭窗口 ]  [ 返回顶部 ]

 

 
 
推荐防火测试
推荐图文
点击排行
 
 
网站首页 | 广告服务 | 关于我们 | 联系方式 | 服务协议 | 版权声明 | 网站地图 | 友情链接 | 网站留言 | 旧版本 | 闽ICP备09009213号
©2019-2021 FIRETC.COM All Rights Reserved   备案号:闽ICP备09009213号-1在线客服 点击QQ交谈/留言 点击QQ交谈/留言