ASTM D2225 Standard Test Methods for Silicone Fluids Used for Electrical Insulation
ASTM D2225电绝缘用硅酮液的标准试验方法
Tests covered in this standard may be used for quality control and design considerations.
Included in each test method is a brief statement describing its significance.
1. Scope
1.1 These test methods cover the testing of silicone fluids for use in transformers, capacitors, and electronic assemblies as an insulating or cooling medium, or both. These methods are generally suitable for specification acceptance, factory control, referee testing, and research.
1.2 Although some of the test methods listed here apply primarily to petroleum-based fluids, they are, with minor revisions, equally applicable to silicone fluids.
1.3 Silicone fluids are used for electrical insulating purposes because of their stable properties at high and low temperatures and their relative environmental inertness.
1.4 A list of the properties and standards are as follows:
Property Measured Section ASTM Test Method Physical: Color 6 D 2129 Flash point 7 D 92 Fire point 7 D 92 Polychlorinated biphenyl 8 D 4059 content Pour point 9 D 97 Refractive index 10 D 1807 Specific gravity 11 D 1298, D 1481, D 4052 Volatility 12 D 4559 Viscosity 13 D 445, D 2161 Chemical: Neutralization number 14 D 974 Water content 15 D 1533 Electrical: Relative permittivity 16 D 924 2 Dielectric breakdown 17 D 877 3 voltage Dissipation factor 18 D 924 2 Specific resistance 19 D 1169 2 Compatibility 20 D 5282
1.5This standard does not purport to address all of the safety problems, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

2. Referenced Documents (purchase separately)
ASTM Standards
D92 Test Method for Flash and Fire Points by Cleveland Open Cup
D97 Test Method for Pour Point of Petroleum Products
D445 Test Method for Kinematic Viscosity of Transparent and Opaque Liquids (and the Calculation of Dynamic Viscosity)
D877 Test Method for Dielectric Breakdown Voltage of Insulating Liquids Using Disk Electrodes
D923 Test Methods for Sampling Electrical Insulating Liquids
D924 Test Method for Dissipation Factor (or Power Factor) and Relative Permittivity (Dielectric Constant) of Electrical Insulating Liquids
D974 Test Method for Acid and Base Number by Color-Indicator Titration
D1169 Test Method for Specific Resistance (Resistivity) of Electrical Insulating Liquids
D1298 Practice for Density, Relative Density (Specific Gravity), or API Gravity of Crude Petroleum and Liquid Petroleum Products by Hydrometer Method
D1481 Test Method for Density and Relative Density (Specific Gravity) of Viscous Materials by Lipkin Bicapillary Pycnometer
D1533 Test Methods for Water in Insulating Liquids (Karl Fischer Reaction Method)
D1807 Test Methods for Refractive Index and Specific Optical Dispersion of Electrical Insulating Liquids
D1816 Test Method for Dielectric Breakdown Voltage of Insulating Oils of Petroleum Origin Using VDE Electrodes
D2129 Test Method for Color of Water White Electrical Insulating Liquids
D2161 Practice for Conversion of Kinematic Viscosity to Saybolt Universal Viscosity or to Saybolt Furol Viscosity
D2864 Terminology Relating to Electrical Insulating Liquids and Gases
D4052 Test Method for Density and Relative Density of Liquids by Digital Density Meter
D4059 Test Method for Analysis of Polychlorinated Biphenyls in Insulating Liquids by Gas Chromatography
D4559 Test Method for Volatile Matter in Silicone Fluid
D4652 Specification for Silicone Fluid Used for Electrical Insulation
D5282 Test Methods for Compatibility of Construction Material with Silicone Fluid Used for Electrical Insulation
Index Terms
Electrical insulating liquids; silicone fluids, testing,; Electronic materials/applications; silicone fluids, electrical insulating, testing;
 

  详情请咨询
  防火资源网-阻燃防火测试中心
  电话:(+86)0592-5056213
  传真:(+86)0592-5105807
  邮件:firetest@firetc.com

凡注明"防火资源网"的所有作品,由<防火资源网>整理编辑,任何组织未经<防火资源网>及其拥有者授权,不得复制、转载、摘编或利用其它方式应用于任何商业行为。

 
 
[ 防火测试中心搜索 ]  [ ]  [ 告诉好友 ]  [ 打印本文 ]  [ 关闭窗口 ]  [ 返回顶部 ]

 

 
 
推荐防火测试
推荐图文
点击排行
 
 
网站首页 | 广告服务 | 关于我们 | 联系方式 | 服务协议 | 版权声明 | 网站地图 | 友情链接 | 网站留言 | 旧版本 | 闽ICP备09009213号
©2019-2021 FIRETC.COM All Rights Reserved   备案号:闽ICP备09009213号-1在线客服 点击QQ交谈/留言 点击QQ交谈/留言