阻燃防火材料-网上贸易平台 | | WAP浏览
服务热线:4006555305
当前位置: 首页 » 防火测试中心 » 各国标准法规 » 美国 » 正文

NFPA 51 焊接、切割和联合工艺用氧气燃料系统设计和安装标准

放大字体  缩小字体 发布日期:2012-02-09   浏览次数:45  分享到: 分享到腾讯微博
NFPA 51 焊接、切割和联合工艺用氧气燃料系统设计和安装标准
NFPA 51 Standard for the Design and Installation of Oxygen-Fuel Gas Systems for Welding, Cutting, and Allied Processes
NFPA 51 焊接、切割和联合工艺用氧气燃料系统设计和安装标准
 
1.1 Scope.
1.1.1 This standard applies to the following
(1) Design and installation of oxygen–fuel gas welding and cutting systems and allied processes (see 3.3.2), except for systems meeting the criteria in 1.1.5
(2) Utilization of gaseous fuels generated from flammable liquids under pressure where such fuels are used with oxygen
(3) Storage on the site of a welding and cutting system installation of the following (a) Gases to be used with such systems where more than one cylinder each of oxygen and fuel gas are stored in any single storage area [includes storage of more than one cylinder each in any single storage area even though all such stored cylinders may be intended for use in systems of the kind described in 1.1.5(1)] (b) Calcium carbide
1.1.2 Unless specifically indicated otherwise, the term welding and cutting systems shall be considered to include allied processes in this standard.
1.1.3 Where only a portion of a fuel gas system is to be used for welding, cutting, or allied processes, only that portion of the system need comply with this standard.
1.1.4 Where only a portion of an oxygen system is to be used with fuel gas for welding, cutting, or allied processes, only that portion of the system need comply with this standard.
1.1.5 This standard shall not apply to the following
(1)*Systems consisting of a single cylinder not exceeding 3.4 m3(120 ft3) of oxygen and a single cylinder not exceeding 3.4 m3 (120 ft3) of fuel gas used for welding and cutting
(2) Systems in which fuel gases are not to be used with oxygen, as described in NFPA 54, National Fuel Gas Code, and NFPA 58, Liquefied Petroleum Gas Code
(3) The manufacture of gases and the filling of cylinders
(4) Storage of empty cylinders
(5) Compressed air–fuel gas systems
 
 
Reduce the risk of fire and explosion with the 2007 NFPA 51.
Using detailed schematic drawings showing different system layouts, the 2007 NFPA 51 provides the latest fire safety requirements for gas-fueled systems for cutting, welding, and other similar processes.
Industry professionals, design engineers, and code enforcement officials will find up-to-date guidance on
·   Cylinder storage
·   System manifolding and piping
·   Associated protective equipment such as regulators
Also provided are requirements for the use of acetylene generators, calcium carbide storage for acetylene generators, and mobile acetylene trailer systems. (Softbound, 17 pp., 2007)

  详情请咨询
  防火资源网-阻燃防火测试中心
  电话:(+86)0592-5056213
  传真:(+86)0592-5105807
  邮件:firetest@firetc.com

凡注明"防火资源网"的所有作品,由<防火资源网>整理编辑,任何组织未经<防火资源网>及其拥有者授权,不得复制、转载、摘编或利用其它方式应用于任何商业行为。

 
 
[ 防火测试中心搜索 ]  [ ]  [ 告诉好友 ]  [ 打印本文 ]  [ 关闭窗口 ]  [ 返回顶部 ]

 

 
 
推荐防火测试
推荐图文
点击排行
 
 
网站首页 | 广告服务 | 关于我们 | 联系方式 | 服务协议 | 版权声明 | 网站地图 | 友情链接 | 网站留言 | 旧版本 | 闽ICP备09009213号
©2019-2021 FIRETC.COM All Rights Reserved   备案号:闽ICP备09009213号-1在线客服 点击QQ交谈/留言 点击QQ交谈/留言