ASTM C 1129通过给凸面阀门及法兰增加热绝缘材料评估蓄热量标准规范

放大字体  缩小字体 发布日期:2012-02-08   浏览次数:158  分享到: 分享到腾讯微博
ASTM C 1129通过给凸面阀门及法兰增加热绝缘材料评估蓄热量标准规范
ASTM C 1129 Standard Practice for Estimation of Heat Savings by Adding Thermal Insulation to Bare Valves and Flanges
ASTM C 1129通过给凸面阀门及法兰增加热绝缘材料评估蓄热量标准规范
 
Manufacturers of thermal insulation for valves typically express the performance of their products in charts and tables showing heat loss per valve. These data are presented for both bare and insulated valves of different pipe sizes, ANSI classes, insulation types, insulation thicknesses, and service temperatures. Additional information on effects of wind velocity, jacket emittance, bare valve emittance, and ambient conditions may also be required to properly select an insulation system. Due to the infinite combination of pipe sizes, ANSI classes, insulation types and thicknesses, service temperatures, insulation cover geometries, surface emittances, and ambient conditions, it is not possible to publish data for each possible case.
Users of thermal insulation for piping systems faced with the problem of designing large systems of insulated piping, encounter substantial engineering costs to obtain the required thermal information. This cost can be substantially reduced by both the use of accurate engineering data tables, or by the use of available computer analysis tools, or both.
The use of this practice by the manufacturer, contractor, and users of thermal insulation for valves and flanges will provide standardized engineering data of sufficient accuracy and consistency for predicting the savings in heating energy use by insulating bare valves and flanges.
Computers are now readily available to most producers and consumers of thermal insulation to permit use of this practice.
The computer program in Practice C 680 has been developed to calculate the heat loss per unit length, or per unit surface area, of both bare and insulated pipe. With values for bare valve or flange surface areas, heat loss can be estimated. By estimating the outer insulation surface area from an insulation manufacturer's or contractor's drawings, the heat loss from the insulation surface can likewise be calculated by taking the product of heat loss per unit area (from programs conforming to Practice C 680) and the valve or flange insulation surface area. The area of the uninsulated surfaces may also need to be considered.
The use of this practice requires that the valve or flange insulation system meets Guide C 1094 and Practice C 450, where applicable.
1. Scope
1.1 The mathematical methods included in this practice provide a calculational procedure for estimating heat loss or heat savings when thermal insulation is added to bare valves and flanges.
1.2 Questions of applicability to real systems should be resolved by qualified personnel familiar with insulation systems design and analysis.
1.3 Estimated accuracy is limited by the following:
1.3.1 The range and quality of the physical property data for the insulation materials and system,
1.3.2 The accuracy of the methodology used in calculation of the bare valve and insulation surface areas, and
1.3.3 The quality of workmanship, fabrication, and installation.
1.4 This procedure is considered applicable both for conventional-type insulation systems and for removable/reuseable covers. In both cases, for purposes of heat transfer calculations, the insulation system is assumed to be homogenous.
1.5 This practice does not intend to establish the criteria required in the design of the equipment over which thermal insulation is used, nor does this practice establish or recommend the applicability of thermal insulation over all surfaces.
1.6 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.7 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

2. Referenced Documents (purchase separately)
ASTM Standards
C168 Terminology Relating to Thermal Insulation
C450 Practice for Fabrication of Thermal Insulating Fitting Covers for NPS Piping, and Vessel Lagging
C680 Practice for Estimate of the Heat Gain or Loss and the Surface Temperatures of Insulated Flat, Cylindrical, and Spherical Systems by Use of Computer Programs
C1094 Guide for Flexible Removable Insulation Covers
American National Standards Institute Standard
ANSIB16.5 Fittings, Flanges, and Valves
Index Terms
calculated energy savings; heat loss from pipes; pipe systems; Bare valves/flanges; Flanges/fittings/valves/parts; Heating systems; Heating tests; Heating tests--thermal insulation; Heat loss/savings; Insulated flat surfaces/pipes; Pipe thermal insulation; Surface analysis--building construction materials/insulation; Thermal insulating materials; Thermal transmission properties; Valves;

  详情请咨询
  防火资源网-阻燃防火测试中心
  电话:(+86)0592-5056213
  传真:(+86)0592-5105807
  邮件:firetest@firetc.com

凡注明"防火资源网"的所有作品,由<防火资源网>整理编辑,任何组织未经<防火资源网>及其拥有者授权,不得复制、转载、摘编或利用其它方式应用于任何商业行为。

 
 
[ 防火测试中心搜索 ]  [ ]  [ 告诉好友 ]  [ 打印本文 ]  [ 关闭窗口 ]  [ 返回顶部 ]

 

 
 
推荐防火测试
推荐图文
点击排行
 
 
网站首页 | 广告服务 | 关于我们 | 联系方式 | 服务协议 | 版权声明 | 网站地图 | 友情链接 | 网站留言 | 旧版本 | 闽ICP备09009213号
©2019-2021 FIRETC.COM All Rights Reserved   备案号:闽ICP备09009213号-1在线客服 点击QQ交谈/留言 点击QQ交谈/留言