ASTM C 1094 可移动的挠性绝热覆盖物标准指南

放大字体  缩小字体 发布日期:2012-02-08   浏览次数:59  分享到: 分享到腾讯微博
ASTM C 1094 可移动的挠性绝热覆盖物标准指南
ASTM C 1094 Standard Guide for Flexible Removable Insulation Covers
ASTM C 1094 可移动的挠性绝热覆盖物标准指南
 
1. Scope
1.1 This guide recommends the criteria to be considered in specifying removable insulation covers for surfaces operating in air at temperatures above ambient.
1.2 A removable insulation cover is fabricated from a fibrous insulation material encased in a tailored fabric or wire mesh enclosure, or both. The fabric seams are typically held together with thread, metal rings, or staples, or combination thereof. These covers must be designed and fabricated to allow a close fit with tight joints over piping, elbows, flanges, valves, and tanks. They are intended to be easily removed and replaced to allow for periodic access to the surfaces they cover.
1.3 In addition to thermal performance, there are other performance requirements of removable covers. These may include, but are not limited to:
1.3.1 Temperature exposure,
1.3.2 Chemical and weather exposure,
1.3.3 Acoustical, and
1.3.4 Fire endurance.
1.4 The materials from which the cover is made may include, but are not limited to:
1.4.1 Insulation media,
1.4.2 Fabric, metal mesh enclosure, or foil enclosure,
1.4.3 Seam materials (thread, metal hooks, etc.), and
1.4.4 Attachment system (hook and loop attachment, straps, wire, etc.).
1.5 The shape, size, and physical design of the cover varies depending on the object to be covered. The cover may consist of more than one piece. Pipes, valves, pumps, and flanges are typical objects to be covered. In many cases, on-site measurements need to be made to ensure an acceptable fit.
1.6 The values stated in SI units shall be regarded as the standard. The values given in parentheses are provided for information only.
1.7 This guide does not intend to establish the criteria required in the design of the equipment over which removable insulation covers are used, nor does this guide establish or recommend the applicability of removable insulation covers over all surfaces.
1.8 It is the responsibility of the user, user's agent, or both, to determine applicability of this guide to their specific application and to inform the equipment designer of the intent to insulate so that appropriate design criteria can be established.
1.9 This standard does not purport to address all of the safety problems, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.
1.10 This standard should be used to measure and describe the properties of materials, products, or assemblies in response to heat and flame under controlled laboratory conditions and should not be used to describe or appraise the fire hazard or fire risk of materials, products, or assemblies under actual fire conditions. However, results of this test may be used as elements of a fire risk assessment which takes into account all of the factors which are pertinent to an assessment of the fire hazard of a particular end use.
Index Terms
covers; insulation; removability; thermal insulating materials; removable insulation covers;

  详情请咨询
  防火资源网-阻燃防火测试中心
  电话:(+86)0592-5056213
  传真:(+86)0592-5105807
  邮件:firetest@firetc.com

凡注明"防火资源网"的所有作品,由<防火资源网>整理编辑,任何组织未经<防火资源网>及其拥有者授权,不得复制、转载、摘编或利用其它方式应用于任何商业行为。

 
 
[ 防火测试中心搜索 ]  [ ]  [ 告诉好友 ]  [ 打印本文 ]  [ 关闭窗口 ]  [ 返回顶部 ]

 

 
 
推荐防火测试
推荐图文
点击排行
 
 
网站首页 | 广告服务 | 关于我们 | 联系方式 | 服务协议 | 版权声明 | 网站地图 | 友情链接 | 网站留言 | 旧版本 | 闽ICP备09009213号
©2019-2021 FIRETC.COM All Rights Reserved   备案号:闽ICP备09009213号-1在线客服 点击QQ交谈/留言 点击QQ交谈/留言